HYDROSONIS-UP

Flow sensor based on the ultrasonic measurement technology.

The absence of internal moving parts ensures maximum measurement accuracy, no maintenance requirement and constant functionality over time.

The measurement precision of a fluid using the ultrasonic technology is not affected by the presence of debris and deposits and allows the installation of the meter in any position, either with ascending or descending flow.

It can be combined with the thermal energy calculator mod. HYDROSPLIT-M3 for compliance with the standard EN1434.

TECHNICAL FEATURES

DN25 (1”)25 (1”)40 (1”1/2)50 (2”)65 (2”1/2)80 (3”)100 (4”)
Maximum flow rate Qsm³/h71220305080120
Nominal flow rate Qpm³/h3,561015254060
Minimum flow rate Qil/h3560100150250400600
Pressure loss at Qpmbar6018013095105160115
Operating limitl/h142440605080120
Working temperature°C5 -1305 -1305 -1305 -1305 -1305 -1305 -130
Maximum admissible pressure MAPbar25252525252525
Pulse valuel1010100100100100100

BASIC VERSION

  • Pulse output for the connection with the HYDROSPLIT-M3
  • Pre-equipped with wired M-BUS + radio WM-BUS interface
  • Metrological class 1:100 according to EN1434
  • Accuracy class 2
  • Battery life 9 years
  • IP54 Protecion Class of the flow unit

INSTALLATION POSITION

WEIGHT AND DIMENSION

Example of installation on return pipe combined with the HYDROSPLIT-M3 heat/BTU calculator.