MB-PULSE 4

The MB-PULSE 4 module allows the conversion of an impulse signal (REED or OC) into the Wired MBUS (EN13757-3) signal.

The device allows the connection of up to four meters equipped with pulse output (water, gas, electricity, heat etc.) of any brand, size and version.

Each record is distinguished by four separate addresses, allowing an easy reading of the consumption for each meter connected.

Easy to configure and install it gives the possibility to configure the primary addresses by using the B METERS software BMBUS and data concentrator mod. MB-MASTER.

TECHNICAL FEATURES

DIMENSIONS89 x 74 x 40 mm
WEIGHT 122 g
TEMPERATURE RANGE +1° / +55°C
POWER SUPPLY From BUS Network, 3 V Lithium Battery (backup)
BATTERY LIFE 1 year (if disconnected from BUS network)
PROTECTION CLASS IP65
TRANSMISSION PROTOCOL MBUS Standard EN 13757-3
MEASUREMENT SENSIBILITY1 – 10 – 100 – 1000
MEASUREMENT UNITS AVAILABLE L – Wh - KJ
TRANSMITTED DATA Consumption Device Status
INPUTS N°4 pulse inputs. Connectable to pulse emitters (REED and Open Collector)
MAXIMUM INPUT FREQUENCY 20 Hz
OUTPUT N°1 Wired MBUS output

WEIGHT AND DIMENSION

Example of installation